Width | 90 mm |
---|---|
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 93 mm |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | 100 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | 6000 m |
Nominal input voltage range | 100 V AC ... 240 V AC |
---|---|
110 V DC ... 250 V DC | |
Input voltage range | 85 V AC ... 264 V AC |
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) | |
Dielectric strength maximum | 300 V AC |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 7 A (100 V AC) |
3.1 A (240 V AC) | |
5.1 A (120 V AC) | |
2.3 A (230 V AC) | |
4.9 A (110 V DC) | |
2.4 A (220 V DC) | |
6.3 A (110 V DC) | |
2.7 A (250 V DC) | |
Nominal power consumption | 569 VA |
Inrush current | < 20 A |
Mains buffering time | typ. 32 ms (120 V AC) |
typ. 32 ms (230 V AC) | |
Input fuse | 12 A (slow-blow, internal) |
Recommended breaker for input protection | 10 A ... 16 A (AC: Characteristics B, C, D, K) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor, gas-filled surge arrester |
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 20 A (-25 °C ... 60 °C, UOUT = 24 V DC) |
POWER BOOST (IBoost) | 26 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC ) |
Selective Fuse Breaking (ISFB) | 120 A (12 ms) |
Derating | 60 °C ... 70 °C (2.5%/K) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | max. 35 V DC |
Protection against overvoltage at the output (OVP) | < 32 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 30 mVPP (with nominal values) |
Output power | 480 W |
Typical response time | < 0.6 s |
Maximum power dissipation in no-load condition | 8 W |
Power loss nominal load max. | 40 W |
Net weight | 1.7 kg |
---|---|
Efficiency | > 93 % (230 V AC) |
MTBF (IEC 61709, SN 29500) | > 900000 h (25 °C) |
> 520000 h (40 °C) | |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 3.5 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage output / PE | 500 V DC (routine test) |
Degree of protection | IP20 |
Protection class | I |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 18 |
Conductor cross section AWG max. | 10 |
Stripping length | 7 mm |
Screw thread | M4 |
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 10 |
Stripping length | 7 mm |
Screw thread | M4 |
Conductor cross section solid min. | 0.2 mm² |
---|---|
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 18 |
Conductor cross section AWG max. | 10 |
Screw thread | M4 |
EMC requirements for noise immunity | EN 61000-6-1 |
---|---|
EN 61000-6-2 | |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
Standard - Electrical safety | IEC 61010-2-201 (SELV) |
Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |